● Measuring temperature, humidity and carbon dioxide
● 2 analog outputs and Modbus RS-485
● Optional analog output + RS-485
● Quick easy installation and maintenance due to well designed
● Cost-efficient and reliable
● Data can be logged and transferred to PC via RS-485 function link free software
Display
Display:LCD module without backlight
Display readout:Double line character(Up:CO2;Down:T & H take turns)
Digit:CO2:4 digits;T & H:3 digits & 1 decimal
Digit height:17.84 mm
Input
CO2:NDIR sensor
Temp. & humidity:MEMS sensor
Measuring range
CO2:0 … 2000 PPM
Temperature:0 … 50℃
Humidity:0 … 100%RH(Non-condensing)
Output
Analog output:0 … 10 V / 4 … 20 mA
Modbus:RS-485
Signal connection:3-wire
Load resistance:Voltage output:≧100 KΩ / Current output:<250 Ω
Warm-up time:<2 min;Stable time 20 min
Temp. influence:T & H:Max. -0.15%RH/℃(0 … 80°C)
Response time:CO2:t90<2 min / T & H:t63(15 … 45°C / 33 … 75%RH)≦10 sec
Sampling time:CO2:About 6 sec;T & H:About 3 sec
Data logger:Via RS-485 by using eyc free software
Accuracy(at +25°C;DC 24 V;101.3 kPa)
CO2:±40 PPM±3% of reading
Temperature:±0.5°C
Humidity:±5%RH(30 … 80% RH)
Environment
Medium:Air
Operating Temp. / Humid.:T&H:0 … 50°C / 0 … 100%RH(Non-condensing)
Operating Temp. / Humid.:CO2:0 … 50°C / 0 … 85%RH
Storage temperature:-20 … + 60℃
Electrical
Power supply:DC 24 V±10% & AC 24 V±10%
Current consumption:DC:150 mA / AC:120 mA
Starting current:DC 24 V:250 mA / AC 24 V:230 mA
Electrical connection:Analog & communication:4P Connector
Installation
Installation:Indoor and Wall mount
Protection
IP rating:IP20
Electrical protection:■ Polarity protection ■ Short-circuit
Certification
Certification:CE
Material
Housing material:PC(PC-110)(UL94V-2)
Weight:100 g
Reviews